When the voltage of a gasoline generator is insufficient to drive a motor, here's what you should do:
There can be various reasons for insufficient generator voltage, and it's essential to identify the root cause to address the issue effectively. Possible reasons include:
1.Insufficient Generator Power:
·Generators have a specified power rating and a maximum load capacity. If the load connected to the generator exceeds its rated capacity, it can result in the prime mover (such as a diesel or gasoline engine) struggling to drive the generator. This may lead to a drop in voltage and a decrease in frequency.
·If the load connected to the generator is within its specified limits, but the frequency remains below the rated value, you should check whether the gasoline or diesel engine has enough power.
2.Low Engine Speed:
·Insufficient generator speed can also lead to low output voltage. If the generator's speed is too low, it may not generate the required voltage. Adjust the generator's speed to reach the rated speed if this is the case.
3.Inadequate Excitation Current:
·Excitation current plays a significant role in determining the generator's output voltage. When there's not enough excitation current, it can result in a voltage drop. There could be various reasons for inadequate excitation current, including issues within the excitation circuit.
·For example, a malfunctioning rectifier diode can lead to reduced excitation current. Poor contact between carbon brushes and slip rings can increase impedance in the excitation circuit, leading to lower excitation current. Excessive resistance in the excitation circuit adjustment can also be a cause.
4.High Motor Starting Current:
·When a generator is connected to a load with a high starting current, such as a motor, and the starting current exceeds the generator's rated output current, it can lead to a voltage drop. To address this, you can use methods like reduced-voltage starting or consider using a generator with a higher capacity.
In summary, when dealing with low generator voltage unable to drive a motor, it's crucial to diagnose the specific cause. You may need to adjust the load, engine speed, excitation current, or consider upgrading to a generator with a higher capacity to ensure proper voltage and power delivery. Regular maintenance and inspection of the generator system are also essential to prevent such issues.